For direct pressure indication at the measuring point and simultaneous switching of circuits for system control
The switching point can be adjusted in the centre of the viewing glass across the entire measuring range (280°C). If the pressure reaches the set limit, the contacts switch.
Energy supply required
Precise switching point, 0.5% of end scale value
The breaking capacity depends on the circuit amplifier used. The non-contact proximity switches in the measuring decive switch the circuit amplifier using the auxiliary energy of the power supply.
Can be used with glycerine filling or other damping fluids
Up to 4 switch contacts with NS 100 or NS 160, up to 2 switch contacts with NS 63
A solid front between measurement system and scale range prevents measuring media from escaping through the viewing glass e.g. following overload and has it escape through a pressure relief opening at the back instead
Available options are triangular front ring with bracket attachment, 3-hole front flange or attachment rim at the back
If Ex-certified buffer stages are used, suitable for potentially explosive atmospheres
technical features:
Nominal size
Accuracy
Connection
Housing
NS 100
Cl 1.0
G 1/2B
CrNi steel, 1.4301
NS 160
Cl 1.0
G 1/2B
CrNi steel, 1.4301
Type standard: in conformity with EN 837-1
Scale ranges (negative overpressure): -1 bar ... 0 bar
Scale ranges (positive overpressure): 0 bar ... 1000 bar
Scale ranges (neg./pos. overpressure): -1 bar ...+15 bar
short-term load capacity: 1.3-fold span
Measuring medium temperature: max. +200°C
Housing type: Housing with bayonet catch
Housing protection type: IP54 acc. EN 60529 / IEC 528
Sensing element material: CrNi steel: 1.4401
Connection material: CrNi steel: 1.4571
Protection and safety design: S3 acc. to EN 837-1, pressure relief opening, laminated safety glass, solid front