Specially designed for pressure measurement in refrigeration systems operated with ammonia-free refrigerants ((H)CFC / HFC)
Twin scale in bar and °C. The line pressure in bar corresponds to a converted refrigerant temperature in the cooling circuit. The temperature scale is coordinated with the respective refrigerant, e.g. R12, R22, R502, R124a.
Easy mounting in control or indication panels from the front with screws or rivets
Bayonet housing allows correcting adjustments after calibrations
Suitable for gaseous, low-viscosity and non-crystallising measuring media that do not corrode brass
technical features:
Nominal size
Accuracy
Connection
Housing
NS 100
Cl 1.0
G 1/2B
CrNi steel, 1.4301
NS 160
Cl 1.0
G 1/2B
Sheet steel, black
Type standard: based on EN 837-1
Scale ranges (neg./pos. overpressure): -1 bar ...+32 bar, coordinated with refrigerant
short-term load capacity: 1.3-fold span
Measuring medium temperature: max. +60°C
Housing type: Housing with bayonet catch
Housing protection type: IP54 acc. EN 60529 / IEC 528
Sensing element material: Brass
Connection material: Brass
Protection and safety design: not possible
ATEX compatibility: acc. to ATEX manufacturer declaration