Type standard | based on EN 13190 |
Measuring principle | Dial thermometer, which is operated by the different expansion of helically arranged bimetallic strips |
Nominal sizes | 63 mm, 80 mm, 100 mm, 160 mm |
Display ranges (EN 13190) | -40°C to +160°C |
Accuracy class (EN 13190) | 2 |
Load capacity | 100 % of the final value for a short time |
Temperature sensor | Ø 7 mm, 45 mm to 500 mm, sealed |
Connection position | rear centric |
Mounting type | Sliding spacer flange |
Material | Housing: Steel 1.0330, blue galvanized Overlay ring: Steel 1.0347, blue galvanized Temperature sensor: Copper alloy 2.0321 Spacer flange: Steel 1.0330, blue galvanized Pointer: Aluminium, black anodized Dial: Aluminium, white coated, black printed Window: Scratch-resistant mineral glass |
Enclosure protection class | IP42 according to EN 60529 |
Adjustment option | none |
Ambient and storage temperature | -20°C to +60°C |
Nominal size = D | D1 | d | d1 | b | b1 | T |
---|---|---|---|---|---|---|
63 | 85 | 7 | 15 | 10 | 7 | 45-500 |
80 | 110 | 11 | 15 | 10 | 7 | 45-500 |
100 | 132 | 13 | 15 | 10 | 7 | 45-500 |
160 | 196 | 18 | 15 | 10 | 7 | 45-500 |
All dimensions in millimeters.
Customized imprint (text, logo), special scale | from 100 pcs. |
Vibration-damped version (Attention: Up to max. 120°C!) | from 1 pc. |
Class 1 according to EN 13190 | from 1 pc. |
Cold bridge made of PAS-PVC (up to max. 120°C, temperature sensor plus 20mm or 50mm) | from 1 pc. |
Temperature sensor: Copper alloy 2.0321 ø 6 mm | Quantity on request |
Min. or max. Drag indicator (min. length of temperature sensor 100mm) | from 1 pc. |
Max. drag indicator (min. length of temperature sensor 100mm) | from 1 pc. |
Red setting pointer, adjustable from the outside | from 1 pc. |
Excess or intermediate length <50mm step | Quantity on request |
Works certificate 2.1 (EN 10204) | from 1 pc. |
(Material) acceptance test certificate 3.1 (EN 10204) | from 1 pc. |
Factory calibration incl. calibration certificate | from 1 pc. |
Direct mounting with screws or rivets and compression fitting.
Please observe the relevant standards and laws, as well as the installation and operating instructions for thermometers.
In particular, we would like to draw your attention to the suitable measuring materials with regard to material resistance and their maximum measuring material temperature.
This specification refers to our current standard with regard to design, dimensions and materials. JAKO Messtechnik GmbH reserves the right to make changes or modifications without prior notice.
Contact us and we will advise you comprehensively on possible solutions!